TTV and TTV 2.0: Validating AI Cooling Before the Silicon Arrives

TTV and TTV 2.0: Validating AI Cooling Before the Silicon Arrives

Expert Insight · Liquid Cooling

Thermal Test Vehicles replace live silicon with a controllable, repeatable heat source, so cold plates, liquid loops and two-phase systems can be validated early. This article explains how a TTV works, how the Thin Plate, Super High-Power and Multi-Zone TTVs map to GPU and AI data center testing, how KLC’s standardized TTV 2.0 platform differs from conventional custom designs, how rack-level Thermal Test Emulators (TTE) extend validation to 300,000W, and where TTV results stop being representative.

Cooling Validation Has a Silicon Problem

AI accelerator power keeps rising, and cooling architectures are moving with it: from air cooling to direct liquid cooling (DLC), and gradually toward microchannel cold plates (MCCP), microchannel lids (MCL) and two-phase systems.

How TTV 2.0 Thermal Test Vehicle works on cooling system test

Validating those designs on live silicon is costly and often impractical. KLC points to accelerator TDP beyond 2,000W as the range where testing a cold plate on an expensive processor becomes risky. Engineering samples can also be scarce, and a failed qualification run can damage the part.

A Thermal Test Vehicle (TTV) addresses this by supplying the heat load without the chip.

TTV in the AI Data Center: From Chip Development to Rack

Cooling is validated at four levels, from chip development to the server rack, and each level has a matching tool.

 

Validation level Question being answered KLC tool
Chip development: layout planning, thermal distribution assessment and cooling solution How will heat distribute across the planned layout, and which cooling solution fits? TTV (thermal distribution simulation)
GPU / chip package How does the package behave under a known heat load, including hotspots? Thin Plate TTV, Multi-Zone TTV
Cold plate / OAM module What is the cold plate’s thermal resistance at AI server power levels? Super High-Power TTV, Super High-Power TTV for OAM
Server rack Can the CDU, liquid-cooling loop or immersion tank carry the full load? Thermal Test Emulator (TTE)

In chip development and integration, a TTV can also simulate thermal distribution and evaluate cooling solutions.

GPU thermal testing is where the three TTV types divide the work. A Thin Plate TTV simulates GPU package thermal behavior in compact formats. A Multi-Zone TTV generates localized hotspots, which matters because GPU and HBM regions do not dissipate heat evenly. A Super High-Power TTV supplies the full power needed to test a cold plate on an AI server or OAM module.

What Is a Thermal Test Vehicle?

A TTV is a controllable heat-generating device that replicates the thermal behavior of CPUs, GPUs, AI accelerators, ASICs and power devices. It delivers controlled, repeatable heat flux with integrated temperature sensing, so engineers can characterize cooling performance before production silicon exists.

Three properties make it useful:

  • Controllable power: the thermal load is set by adjusting input voltage.
  • Repeatability: the same heat input on every run, unlike workload-driven silicon.
  • Measurability: sensors at known positions give consistent data for comparing cold plate designs.

A TTV is a resistive heater. It does not self-regulate like a PTC element, so it must be driven by an external DC power supply and protected by an external PID temperature controller and circuit breaker. These belong to the test setup, not to the TTV itself.

How a TTV Fits into a Cooling Test

The test follows the same heat path as a real processor:

  1. Heat generation: the TTV converts electrical power into a known heat load.
  2. Heat transfer: heat moves through the thermal interface material (TIM) into the cold plate or heatsink.
  3. Heat removal: circulating coolant carries the heat to the loop, CDU or immersion system under test.

Temperatures are read with K-type or T-type thermocouples placed in the TTV’s pre-drilled sensor holes. From those readings and the applied power, engineers derive thermal resistance, commonly defined as the temperature difference between the TTV and the coolant divided by the power.

Test Data: 50 × 50 mm TTV on a Liquid Cold Plate

KLC measured a 50 × 50 mm TTV on a liquid-cooled cold plate while stepping power from about 250W to about 8,000W, or about 320 W/cm². The test was run to 8,000W; the power ratings published in this article are set more conservatively. Four temperatures were recorded: TTV core (the sensor position at the center heat source), TTV surface, cold plate surface and liquid output.

Figure 1: Temperature vs. Power Curve
Temperatures were measured at the TTV core, TTV surface, and cold plate surface.
(The ambient temperature and water temperature were both maintained at 27.2°C.)

Temperatures rise close to linearly with power. Values below are read from the chart and are approximate. At about 8,000W:

  • TTV core: about 160°C
  • TTV surface: about 145°C
  • Cold plate surface: about 102°C
  • Liquid output: about 35°C, up from about 27°C at low power

KLC 50 × 50 mm Thermal Test Vehicle (TTV) measured temperature versus power results up to 8,000 W, showing heater core, heater B-point, copper B-point, cold plate B-point, and liquid outlet temperatures.

Figure 2: Temperature Difference vs. Power Density
Measured temperature differences under various power density conditions.

Temperature versus power test results for KLC 50 × 50 mm Thermal Test Vehicle, showing heater core, copper, cold plate, and liquid outlet temperatures.

  • TTV surface to cold plate surface: about 43°C at about 320 W/cm², or roughly 13°C per 100 W/cm².
  • TTV core to surface: about 15°C at the same power density.
  • Reading: the surface-to-cold-plate drop is about three times the core-to-surface drop, which shows how much of the temperature budget is used up at the interface and cold plate surface.

Both curves are close to linear across the tested range.

KLC internal test data, not independently verified.

The TTV Family

Different validation jobs need different form factors. KLC’s published ranges:

KLC has upgraded the Thermal Test Vehicle platform into a standardized TTV 2.0 architecture that enables faster development, modular configurations, higher power density, and lower thermal resistance for AI thermal validation.

Type Best suited for Published data points
Thin Plate TTV Compact packages, space or power-density constraints 30×30 to 80×80 mm, 12–600V; 50×50 mm up to 1,600W; 80×80 mm up to 4,200W
Super High-Power TTV Cold plate, CDU and OAM liquid-cooling validation 50×50 mm up to 5,000W; 80×80 mm up to 12,800W; heat flux up to 500 W/cm²
Multi-Zone TTV Hotspot simulation, two-phase cooling evaluation Independent power zones simulating non-uniform heat distribution
Thermal Test Emulator (TTE) Rack-level validation of immersion tanks, liquid cooling and CDUs Multiple TTVs combined, up to 300,000W

TTV 2.0: From Project-Based to Platform-Based

Conventional TTVs are designed project by project. Every dimension, thickness and sensor layout is custom, which lengthens lead time and raises development cost.

TTV 2.0 takes a different route: standardized dimensions and thicknesses on a modular platform, with customization still available. KLC states that this reduces cost and lead time.

Feature Conventional TTV TTV 2.0 platform
Design approach Fully customized Standardized + customizable
Lead time Longer Faster
Development cost Higher Lower
Dimensions Custom every project Standard sizes + custom options
Temperature sensor Optional 100% built-in T-type
Architecture Project-based Modular platform

The TTV 2.0 standard sizes are:

Size (mm) Voltage (V) Max current (A) Max power (W)
30 × 30 12–600 15.0 2,000
50 × 50 12–600 10.4 5,000
60 × 60 12–600 12.5 5,000
80 × 80 12–600 50.6 8,000

Other platform features include a high-conductivity hybrid structure for low thermal resistance and multi-zone hotspot simulation with independent power-zone control.

The built-in sensor is the practical gain. When every unit ships with the same sensor position, results from different test benches and different cold plate vendors become easier to compare.

Rack-Level Validation with TTE

A TTV tests one heat source. A Thermal Test Emulator (TTE) tests the system around it. KLC describes a TTE as a rack-level thermal emulator that combines multiple TTVs, stacked in a single structure, to simulate entire boards or server racks. This allows immersion tanks, liquid cooling, CDUs and cold plates to be validated at rack power levels of up to 300,000W.

Rack-level emulation covers questions a single TTV cannot:

  • CDU validation: verify the cooling capacity of the coolant distribution unit.
  • Liquid cooling systems: evaluate cooling capacity, flow distribution and system stability under high-power conditions.
  • Immersion tanks: validate the cooling of an entire tank at rack power levels.
  • Rack-level tests: emulate complete boards or racks instead of single devices.

The scale is the point: KLC publishes up to 300,000W at rack level for TTE, against up to 12,800W for a single Super High-Power TTV.

The practical sequence is bottom-up: characterize the cold plate on a single TTV, then confirm the loop and CDU with a TTE.

Choosing the Right TTV

Start with three inputs: target power range, operating voltage, and sensor options. Then match the application:

Application Recommended product Typical scenario
AI server cold plate validation Super High-Power TTV Cold plate thermal resistance testing
AI GPU thermal simulation Thin Plate TTV GPU package thermal behavior
GPU hotspot analysis Multi-Zone TTV Localized hotspot generation
OAM cooling validation Super High-Power TTV for OAM OAM liquid-cooling performance
Rack-level cooling test TTE Full rack thermal emulation
Two-phase cooling validation Multi-Zone TTV Phase-change cooling evaluation
CDU validation Super High-Power TTV CDU cooling capacity verification

Beyond the Data Center: Automotive Computing

The same method applies wherever a processor needs a validated cooling loop. Automotive ASICs behind ADAS, autonomous driving and centralized vehicle computing generate significant heat, and KLC lists automotive ADAS thermal validation among TTV applications. Cold plates and coolant loops for these platforms can be evaluated before production silicon is available.

Where TTV Results Stop Being Representative

A TTV is a thermal model, not a chip. Engineers should plan for these limits:

  • No electrical behavior: a TTV does not reproduce transient, workload-driven power changes unless the external power supply is programmed to do so.
  • Approximated hotspots: multi-zone designs approximate real die power maps; they do not replicate them.
  • Interface sensitivity: results depend on TIM, mounting pressure and surface flatness. These must match the intended production package.
  • Nominal specifications: published power figures are baselines. Customization changes the achievable result.
  • Final qualification: validation with real silicon is still required before release.

The TTV narrows the design space early. It does not replace the last test.

KLC Perspective: Test the Cooling Loop, Not Just the Chip

As heat flux rises, the cold plate, TIM, flow distribution and coolant temperature interact more strongly. A repeatable heat source lets teams isolate those variables, one change at a time.

Standardization is the next step. A platform with fixed sizes, built-in sensing and a known power envelope shortens the path from cold plate prototype to comparable data.

The next generation of liquid cooling will be proven on the test bench first, and the quality of that bench starts with the heat source.

 